BEKOMAT 12 Alarm Test To test pre-alarm function press the Test button for more than 1 minute but less than 5 minutes. To test alarm function press the Test button for more than 5 minutes.
BEKOMAT 13 Alarm Test To test pre-alarm function press the Test button for more than 1 minute but less than 5 minutes. To test alarm function press the Test button for more than 5 minutes.
BEKOMAT 20FM Filter Lifetime Reset Press and hold Test and Mode buttons for at least 10 seconds, all lifetime LEDs will begin to flash. To confirm reset press the Mode button. To cancel reset press the test button or don’t press any buttons for 60 seconds.
BEKOMAT 31-33 Maintenance Reset Remove control unit from top of drain. Press and hold test button for at least 5 seconds. Reinstall control unit on top of drain.
Test Alarm Function Press and hold the Test button for at least one minute.
BEKOMAT 8-9 Alarm Test Press and hold the Test button for 1 minute.
DMC18 HdP Alarm High dew point.
LdP Alarm Low dew point.
PF Alarm Failure of temp probe T1 (dew point). Check cabling or replace probe if bad.
SrV Alarm Service alarm. Service unit and reset timer by holding the wrench/down arrow button for at least 20 seconds.
drA Alarm Bekomat condensate drain has faulted. Inspect and replace if required.