Gardner Denver
Air Pilot

Service Menu
Hold up and down arrow keys for 5 seconds until all LEDs flash then select code 02.
User Guide
Airplus

Alarm A.01
Air Filter Vacuum Switch
Alarm A.02
High Discharge Pressure
Alarm A.03
High Oil Temp
Alarm S.01
Oil Change Due
Alarm S.02
Air Filter Due
Alarm S.03
Oil Filter Due
Alarm S.04
Separator Due
Alarm S.06
General Service Due
Distributor
0009
Error A.03
Motor Overload
Error A.04
Phase Monitor
Error A.05
Emergency Stop
Error A.07
Temp Sensor Fault
Error A.12
High Discharge Pressure
Error A.13
Pressure Transducer Fault
Error A.20
High Pressure Switch
Error A.25
High Temp Switch
Error A.33
Power Loss While Loaded
Error E.04
Power Loss or Low Voltage
Manual Number
13-19-608
Run Inhibit 1.01
Low Oil Temp. See Td.
Technician
0121
User
0100
Reset Guide
User Manual
Airsmart

101
Fan fault, a cooling fan is over temperature.
102
Drive 1 fault, the main motor VFD has shut down.
103
The second stage motor VFD has shut down.
104
The cooler fan motor VFD has shut down.
105
Emergency stop, the emergency stop button has been pressed.
106
Open pressure transducer PT5 shutdown.
107
High plant pressure shutdown, the plant pressure is greater than 190 psi (13 bar).
108
Shorted pressure transducer PT5 shutdown.
109
Open pressure transducer PT4 shutdown.
110
High separator pressure shutdown, separator pressure is greater than 190 psi (13 bar).
111
Shorted pressure transducer PT4 shutdown.
112
Open pressure transducer PT3 shutdown.
113
High reservoir pressure shutdown, the oil reservoir pressure is greater than 190 psi (13 bar).
114
Shorted pressure transducer PT3 shutdown.
115
Open pressure transducer PT2 shutdown.
116
High interstage pressure shutdown, interstage pressure is greater than 190 psi (13 bar).
117
Shorted pressure transducer PT2 shutdown.
118
Open pressure transducer PT1 shutdown.
120
Shorted pressure transducer PT1 shutdown.
121
Open thermistor T5 shutdown.
122
High package discharge temperature shutdown, the package discharge temperature is greater than 158°F (70°C).
123
Shorted thermistor T5 shutdown.
124
Open thermistor T4 shutdown.
125
High separator temperature shutdown, the separator temperature is greater than 240°F (116°C).
126
Shorted thermistor T4 shutdown.
127
Open thermistor T3 shutdown.
128
High discharge temperature shutdown, the air end discharge temperature is greater than 240°F (116°C).
129
Shorted thermistor T3 shutdown.
130
Open thermistor T2 shutdown.
131
High interstage temperature shutdown, the interstage temperature is greater than 240°F (116°C).
132
Shorted thermistor T2 shutdown.
133
Open thermistor T1 shutdown.
134
High inlet temperature shutdown, the inlet air temperature is greater than 113°F (45°C).
135
Shorted thermistor T1 shutdown.
136
High separator rate shutdown, rapid temperature rise at the separator.
137
High discharge rate shutdown, rapid temperature rise at the air end.
138
Fan starter shutdown, the fan starter auxiliary contact does not match the expected state.
139
Drive 1 start, main motor VFD failed to start.
140
Drive 2 start, second stage motor VFD failed to start.
141
Drive 3 start, cooling fan motor VFD failed to start.
142
Power failure, there was a loss of power to the unit.
143
XB1 communication error, internal communication error, replace controller.
144
Drive 1 communication error, there was a communication error between the controller and the main motor VFD.
145
Drive 2 communication error, there was a communication error between the controller and the second stage motor VFD.
146
Drive 3 communication error, there was a communication error between the controller and the cooling fan motor VFD.
147
Optional shutdown, a digital input programmed for optional shutdown has been triggered.
148
Low voltage shutdown, the digital input programmed for low voltage shutdown has been triggered.
149
Phase sequence shutdown, the digital input programmed for phase sequence shutdown has been triggered.
150
Motor over temperature shutdown, the digital input programmed for motor over temperature shutdown has been triggered.
151
Water pressure shutdown, the digital input programmed for water pressure has been triggered.
152
High vibration shutdown, the digital input programmed for high vibration has been triggered.
153
Zero transducer PT5 shutdown, transducer PT5 not properly zeroed or a vacuum is present.
154
Zero transducer PT4 shutdown, transducer PT4 not properly zeroed or a vacuum is present.
155
Zero transducer PT3 shutdown, transducer PT3 not properly zeroed or a vacuum is present.
156
Zero transducer PT2 shutdown, transducer PT2 not properly zeroed or a vacuum is present.
157
Zero transducer PT1 shutdown, transducer PT1 not properly zeroed or a vacuum is present.
160
Controller internal error, the controller has failed and needs to be replaced.
161
EEPROM restored, main parameter set in controller memory.
164
Invalid model table shutdown, an invalid model was selected during factory setup or during a controller replacement.
165
Low DC voltage shutdown, the power to the controller is less than 18.5VDC +/- 1.5VDC.
166
High dryer temperature shutdown, the temperature at the dryer is greater than 120°F (49°C).
167
Open thermistor T6 shutdown.
168
Shorted thermistor T6 shutdown.
169
CM table invalid shutdown, model table in memory is corrupted.
170
Actuator communication error shutdown, an error occurred with communications between the controller and precision mixing valve.
171
Low oil pressure shutdown, the oil pressure has dropped below (interstage pressure + 2.5 psi).
172
Sequencer communication error shutdown, communications between the controller and communications module has failed.
173
Open pressure transducer PT6 shutdown.
174
Shorted pressure transducer PT6 shutdown.
175
Zero transducer PT6 shutdown, transducer PT6 not properly zeroed or a vacuum is present.
176
Open pressure transducer PT7 shutdown.
177
Shorted pressure transducer PT7 shutdown.
178
Zero transducer PT7 shutdown, transducer PT7 not properly zeroed or a vacuum is present.
179
Main motor starter shutdown, the main motor starter auxiliary contact does not match the expected state.
201
Low sump pressure shutdown, pressure in the oil reservoir has been less than 15 psi (1 bar) for more than 1 minute.
202
Change separator shutdown, separator differential pressure is greater than 15 psi (1 bar).
301
Change separator, separator differential pressure greater than 8 psi.
302
Change air filter, air filter vacuum switch tripped.
303
Change air filter, air filter maintenance timer has elapsed.
304
Change oil filter, oil filter maintenance timer has elapsed.
305
Change oil, oil maintenance timer has elapsed.
306
Low ambient temperature, package discharge temperature below 40°F (4°C).
307
Low ambient temperature, package separator temperature below 40°F (4°C).
308
High separator temperature, separator temperature greater than 225°F (107°C).
309
High plant temperature, the package discharge temperature is greater than 149°F (65°C).
310
High inlet temperature, the package inlet temperature is greater than 113°F (45°C) or on some models, 104°F (40°C).
315
Change separator, the separator maintenance timer has elapsed.
316
High discharge temperature, temperature at the air end is greater than 225°F (107°C).
317
High interstage temperature, temperature at the interstage is greater than 225°F (107°C).
318
Optional alarm, a digital input programmed for optional alarm has been triggered.
320
Change oil filter, oil filter differential switch was triggered.
321
Low voltage alarm, the digital input programmed for low voltage alarm has been triggered.
322
Motor over temperature, the digital input programmed for motor over temperature has been triggered.
323
Water pressure alarm, the digital input programmed for water pressure has been triggered.
324
High vibration, the digital input programmed for high vibration has been triggered.
325
Low discharge temperature, the discharge temperature of the air end is less than 185°F (85°C). Applicable to two-stage units only.
326
High dryer temperature, the temperature at the dryer is greater than 100°F (38°C).
327
Motor lubrication alarm, the motor lubrication maintenance timer has elapsed.
328
Low plant pressure, the compressor is unable to maintain the set target pressure.
329
Low oil pressure, the oil is less than (interstage pressure + 5 psi). Applicable to two-stage units only.
330
Main motor VFD heat sink temperature is greater than 175°F (79°C).
331
Second stage motor VFD heat sink temperature is greater than 175°F (79°C).
332
Change control panel filter, the control panel filter maintenance timer has elapsed.
333
Dryer alarm, the integrated air dryer has shut down.
334
Oil sample due, the oil sample maintenance timer has elapsed.
Config Adjust
407
Manual I/O
9091
Manual Number
13-17-600 for compressors, IQ-7-200 for blowers. 13-17-604 for sequencing and communications.
Prog I/O Adjust
8412
Comm Module Manual
Quick Reference
User Manual
User Manual (Blowers)
Airsmart G2

Distributor
8412
User
407
Modbus Manual
Quick Reference
Sequencing Manual
User Manual
Connect 12

Service
7555
Setup Wizard
7777
Snapshot
7123
Technician
7070
Modbus Manual
Profibus Manual
User Manual
Connect 4

Compressor Setup
0032
System Setup
0011
Install Guide
Tech Note iPCB
User Manual
Digipilot

Diagnostics
Up Down - + Up Down
Machine Config
- + Up Down - +
Regulation
+ - Down Up + -
Service
Up Down - + Up Down
User Manual
E-Smart

User Manual
ES/ES+

Manual Number
13-910-647
Protocol Manual
User Manual
ESP Series 1000

Engineer
120741
Factory
060644
Operator
091101
ESP Series 7800 (Early)

Level 1
120741
Level 2
060644
Level 3
0201
ESP Series 7800 (Late)

Engineer
120741
Factory
060644
Eaton DG1 VFD

Parameter Change
0111
Fault Guide
GD Pilot

Change Units
Press and hold Enter/Reset then scroll with down arrow.
Infinite Auto Restart
8879
Rotation Off
9989
Rotation On
9988
Setup
2213
Specialist
0102
Speed Lock
9466
Technician
3002
User
3022
Quick Reference
Setup Code Guide
User Manual Fixed Speed
User Manual Variable Speed
GD Pilot S

Factory
0102
Quick Reference
GD Pilot SE

GD Pilot TS

BLS Enable
1234
Infinite Auto Restart
8879
Maintenance
3100
Setup
02213 Code defaults controller.
Snapshot
7123
Specialist
0102
Speed Lock
09466
Technician
03002
User
3022
Quick Reference
User Manual
GD Pilot XTS

Alarm Logging
50
BLS Enable
1234
Infinite Auto Restart
8879
Maintenance
3100
Setup
02213 Code defaults controller.
Snapshot
7123
Specialist
0102
Speed Lock
09466
Technician
03002
User
3022
User Manual
Governor

Maintenance
407
Technician
8412
Quick Reference
Sequencing Manual
User Manual
Meditrol-Plus

Distributor
8412
Service
407
User Manual
PCM Module

User Manual
Q Pilot

Customer
0120
Service
2460
RS2000

User Manual
S Controller

Manual Number
13-8-609, section 4.
Pressure Error E01
Failure of Discharge Pressure Transducer.
Pressure Error E02
Failure of Sump Pressure Transducer.
Pressure Error E03
Failure of both Pressure Transducers.
Pressure Error E04
Emergency Stop.
Temperature Error E01
Failure of Discharge Temperature Sensor.
Temperature Error E02
Failure of Separator Temperature Sensor.
Temperature Error E03
Failure of Both Temperature Sensors.
User Manual
Scroll Deluxe HMI

Distributor
8412
Service
407
User Manual
VS Pilot

Machine
175
System
314
User Manual